Parameters
1-16 High Speed Filter Time Const
Range:
Function:
Size related
[ 0.01 -
High pass-filter damping time constant
*
20 s]
determines the response time to load
steps. Obtain quick control through a
short damping time constant. However, if
this value is too short, the control gets
unstable. This time constant is used
above 10% rated speed.
1-17 Voltage filter time const
Range:
Function:
Size
[ 0.01 -
Machine Supply Voltage Filter Time
related
1 s]
constant is used for reducing the
*
influence of high frequency ripples and
system resonances in the calculation of
machine supply voltage. Without this
filter, the ripples in the currents can
distort the calculated voltage and affects
the stability of the system.
3.2.4 1-2* Motor Data
This parameter group comprises input data from the
nameplate on the connected motor.
NOTICE
Changing the value of these parameters
affects the setting of other parameters.
1-20 Motor Power
Range:
[2]
0.12 kW - 0.16 hp
[3]
0.18 kW - 0.25 hp
[4]
0.25 kW - 0.33 hp
[5]
0.37 kW - 0.5 hp
[6]
0.55 kW - 0.75 hp
[7]
0.75 kW - 1 hp
[8]
1.1 kW - 1 hp
[9]
1.5 kW - 2 hp
[10]
2.2 kW - 3 hp
[11]
3 kW - 4 hp
[12]
3.7 kW - 5 hp
[13]
4 kW - 5.4 hp
[14]
5.5 kW - 7.5 hp
[15]
7.5 kW - 10 hp
[16]
11 kW - 15 hp
[17]
15 kW - 20 hp
[18]
18.5 kW - 25 hp
[19]
22 kW - 30 hp
[20]
30 kW - 40 hp
[21]
37 kW - 50 hp
[22]
45 kW - 60 hp
TR150 Programming Guide
1-20 Motor Power
Range:
[23]
[24]
[25]
[26]
1-22 Motor Voltage
Range:
Size related
1-23 Motor Frequency
Range:
Size
related
1-24 Motor Current
Range:
Size related
Function:
1-25 Motor Nominal Speed
Range:
Size related
1-26 Motor Cont. Rated Torque
Range:
Size related
BAS-SVP16A-EN - Rev. 2013-09-05
55 kW - 75 hp
75 kW - 100 hp
90 kW - 120 hp
110 kW - 150 hp
Function:
[ 50.0 -
Enter the nominal motor voltage
*
1000.0 V]
according to the motor nameplate
data. The default value corresponds to
the nominal rated output of the unit.
Function:
NOTICE
[ 20 -
400
*
This parameter cannot be adjusted
Hz]
while the motor is running.
Select the motor frequency value from the
motor nameplate data. For 87 Hz operation
with 230/400 V motors, set the nameplate
data for 230 V/50 Hz. Adapt 4-14 Motor
Speed High Limit [Hz] and 3-03 Maximum
Reference to the 87 Hz application.
Function:
[ 0.01 -
Enter the nominal motor current value
*
26.0 A]
from the motor nameplate data. This
data is used for calculating motor
torque, motor thermal protection etc.
Function:
[100 -
Enter the nominal motor speed value
*
60000 RPM]
from the motor nameplate data. This
data is used for calculating automatic
motor compensations.
Function:
NOTICE
[0.1 -
*
10000
Changing this parameter affects
Nm]
settings of other parameters.
This parameter is available only when
1-10 Motor Construction is set to [1] PM,
non-salient SPM.
Function:
3
27
3