Nortel SONET AccessNode User Manual page 74

Hide thumbs Also See for SONET AccessNode:
Table of Contents

Advertisement

5-6 Replacing modules in a copper-distribution shelf
Procedure 5-2 (continued)
Replacing the line cards
Step
5
6
7
8
9
10
11
AccessNode P0904244 Issue 1.0
Action
Remove the line card from its slot by grasping the tab on the line card
faceplate with your thumb and forefinger, and pulling outward.
Note: Figure 5-3 shows a 2-wire Omega or Epsilon line card. Figure 5-4
shows an O4W line card. Figure 5-5 shows an O68W line card.
Wait at least 12 seconds for the system to stabilize.
Insert a replacement line card into the slot.
Gently push in the replacement line card until the ejector latch comes in
contact with the drawer. Then push the latch in to engage the circuit pack with
the midplane connector.
Change the state of the line card to in-service (IS):
chgstate is↵
y↵
The state changes to IS.
Gently push in the CDS line drawer until the handle comes in contact with the
shelf. Then push the line drawer in to engage the handle with the shelf.
Lock the CDS line drawer handle by turning the locking screw 90 degrees
clockwise so that the alignment indicators are aligned.
—continued—