AccessNode Series 800A Outside Plant Cabinet Installation 323-3001-210 Issue 1.0
Action
Label each end of the optical patch cords or pigtails (see Table 7-9 on page
7-35 through Table 7-11 on page 7-36) with the following information:
the slot number in the ABM shelf for the intended OC-3 or OC-12 optical
interface card
the direction of signal, Tx (transmit) or Rx (receive)
Encase the fibers in split tubing.
Route the tubing with the fiber pigtails or patch cords inside into the cabinet
through the far right-hand cable entry duct in the bottom of the termination
compartment as shown in Figure 7-19 on page 7-38.
Note: Ensure that the length of the pigtail or patch cords routed into the
cabinet is sufficient to reach the ABM shelf (approximately 6 meters or 19
feet).
Route the tubing up the cable ladder on the right-hand side of the termination
compartment into the fiber cable entry hole at the top of the compartment.
Note: Maintain at least the minimum bend radius (3.0 inches/76 mm) for the
fiber pigtails or patch cords installed.
Tie wrap the tubing to the cable ladder.
—continued—
Routing and splicing the fiber cable 7-37