Protective Control/Anomalous Stop Control By Compressor S Number Of Revolutions - Mitsubishi Heavy Industries V Multi FDC71VNX Technical Manual

Inverter packaged air conditioner
Hide thumbs Also See for V Multi FDC71VNX:
Table of Contents

Advertisement

(c) Switching of defrost control with SW3-1
(i)
If SW3-1 on the outdoor control PCB is turned to ON, it becomes easier to enter the defrost operation. Use this when
installing a unit at snowing regions.
(ii) Control contents
1)
It allows entering the defrost operation under the defrost condition A when the cumulative heating operation time
becomes 30 minutes. It is 37 minutes at SW3-1 OFF (Factory default).
2)
It allows entering the defrost operation under the defrost condition B when the cumulative heating operation time
becomes 25 minutes. It is 30 minutes at SW3-1 OFF (Factory default).
3)
It allows the defrost operation with the outdoor heat exchanger temperature (Tho-R) and suction pressure
saturation temperature (SST) being higher than normal.
(6) Protective control/anomalous stop control by compressor's number of revolutions
(a) Compressor discharge pipe temperature protection
(i)
Protective control
As the discharge pipe temperature (detected with Tho-D) exceeds the setting value, the compressor speed (frequency)
is controlled to suppress the rise of discharge pipe temperature.
Release
105(A)
Discharge pipe temperature (°C)
(ii)
Anomalous stop control
1)
If the discharge pipe temperature (detected with Tho-D) exceeds the setting value, the compressor stops.
2)
When it is detected 2 times within 60 minutes or after continuous 60 minutes, including the stop of compressor,
E36 is displayed on the remote control and it enters the anomalous stop mode.
Compressor operation
90(85)
Discharge pipe temperature (°C)
(iii)
Reset of anomalous stop mode
As it drops to the reset value of 90 (85)°C or lower for 45 minutes continuously, it becomes possible to restart from
the remote control.
(b) Cooling high pressure protection
(i) Protective control
1)
Outdoor heat exchanger temperature (Tho-R) exceeds the setting value A.
2)
When the outdoor air temperature (Tho-A) is 40°C or higher and the outdoor heat exchanger temperature (Tho-R)
exceeds certain value (depends on compressor frequency).
3)
Control value A is updated to an optimum value automatically according to the operating conditions.
Reset
Outdoor heat exchanger temperature (°C)
(ii) Anomalous stop control
1)
As the outdoor heat exchanger temperature (Tho-R) exceeds the setting value, the compressor stops.
2)
If it is detected 5 times within 60 minutes or 65°C or higher continues for 60 minutes, including the stop of
compressor, E35 is displayed on the remote control and it enters the anomalous stop mode.
Compressor operation
Outdoor heat exchanger temperature (°C)
(iii)
Reset of anomalous stop mode
As it reaches the reset value of 51°C or lower, it becomes possible to restart from the remote control.
Reduces compressor
speed at each minute.
Retention
 
110(B)
Compressor stop
 
135(A)
Reduces compressor
speed at each minute.
A
Compressor stop
 
51
65
Note (1) Value in ( ) are for the model FDC200.
Super heat
25°C or more
20°C or less
Note (1) Value in ( ) are for the model FDC200.
Super heat
25°C or more
20°C or less
339
-
-
'19 • PAC-T-327
A
B
95
100
100
105
A
110
115
Control value A
54-60°C