Mitsubishi Heavy Industries V Multi FDC71VNX Technical Manual page 171

Inverter packaged air conditioner
Hide thumbs Also See for V Multi FDC71VNX:
Table of Contents

Advertisement

(8)
Outdoor unit control failure diagnosis circuit diagram
Models SRC40ZSX-S, 50ZSX-S, 60ZSX-S
● Outdoor unit check points
CAUTION- HIGH VOLTAGE
High voltage is produced in the control box. Don't touch
electrical parts in the control box for 5 minutes after the
unit is stopped.
Color symbol
Mark
Color
BK
Black
BL
Blue
RD
Red
WH
White
YE
Yellow
Y/G
Yellow/Green
◆Inspection power transistor.
Remove the faston terminal and test
output voltage.
L1
◆Inspection of resistance value of sensor.
Remove the connector and check the resistance value.
◆Voltage check in PCB.
The normal range is as follows.
Display
Voltage range
①DC280V DC230V - DC310V
②DC220V DC218V - DC222V
③DC213V DC212V - DC214V
④DC215V DC214V - DC216V
⑤DC225V DC224V - DC226V
⑥DC 2.5V DC 2.3V - DC22.5V
Power source
1 Phase
AC200-240V 50Hz
CM
MS
3~
Indoor
unit
U
V
W
CNTH
2
2
2
L2
TH1 TH2 TH3
170
-
◆Power source and serial signal inspection.
to
: AC 220/230/240V
L
N
to
: AC 220/230/240V
1
2/N
to
: Normal if the voltage oscillates between
2/N
3
DC 0 and approx. 20V
Outdoor unit
TERMINAL
BLOCK
TB1
FUSE
(BK)
(BK)
L
250V 20A
(WH)
N
(Y/G)
TERMINAL
BLOCK
TB2
1
2
N
(RD)
3
(Y/G)
C-2
S.IN
CNFAN
CNEEV
1 2 3 4
6
M
M
EEV
FMo
◆Inspection of outdoor fan motor.
(Refer to page 231)
-
'19 • PAC-T-327
(WH)
(BK)
R.IN
20S
◆Inspection of electronic
expansion value.