Mitsubishi Heavy Industries V Multi FDC71VNX Technical Manual page 245

Inverter packaged air conditioner
Hide thumbs Also See for V Multi FDC71VNX:
Table of Contents

Advertisement

Error code
Error code
Remote controller: E58
E58
Remote control:
1. Applicable model
Models SRC40-60
2. Error detection method
When the current safe control
has operated at the compressor
speed of 30 rps or under:
3. Condition of error displayed
Same as above
4. Presumable cause
• Excessive refrigerant amount
• Indoor,outdoor unit installation
spaces
• Faulty compressor
• Defective outdor air
temperature sensor
• Defective outdoor unit PCB
Note:
LED
Green
Red
LED
Green
Red
Keeps flashing Stays Off
Indoor
Keeps flashing
Stays OFF
Indoor
3 time flash
Outdoor
5. Troubleshooting
Diagnosis
Is the refrigerant
amount nomal ?
YES
Is outdoor
ventilation condition
good ?
YES
Inspect
compressor
YES
Inspect
outdoor air temperature
sensor
244
-
Content
Content
Current safe stop
Current safe stop
(Models SRC40-60 only)
(Models SRC40-60 only)
NO
NO
NO
NO
YES
-
'19 • PAC-T-327
Countermeasure
Adjust the refrigerant
amount properly.
Secure space for inlet and
outlet.
Replace compressor.
Replace sensor.
Defective outdoor unit
PCB¡Replace.
(Defective outdor air
temperature sensor input
circuit)

Hide quick links: