Error code
Remote control:
WAIT
1. Applicable model
Models FDC200, 250VSA
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Faulty indoor unit control
PCB
• Defective remote control
• Broken remote control wire
• Faulty outdoor unit control
PCB
• Broken connection wires
Note:
LED
Green
Red
Keeps flashing
Stays OFF
Indoor
Keeps flashing
2-time flash
Outdoor
5. Troubleshooting
Diagnosis
"
" is still displayed on the
WAIT
remote control LED 2 minutes
after power ON.
YES
Is the outdoor unit
green LED
flashing?
YES
Is the indoor unit
green LED flashing?
YES
Is the outdoor unit
red LED flashing
twice?
YES
Are wires
connected properly between indoor/
outdoor units?
YES
Is approx.
DC20V detected between -Ž on
the outdoor unit terminal
block?
YES
Is approx.
DC20V detected between -Ž on
the indoor unit terminal
block?
197
-
Communication error at
Content
initial operation (1/2)
(Models FDC200, 250VSA only)
NO
To next page
NO
NO
NO
NO
NO
YES
-
'19 • PAC-T-327
Countermeasure
Defective indoor unit
control PCB ➞ Replace.
Defective indoor unit
control PCB ➞ Replace.
Defective remote control ➞ Replace.
Broken remote control wire
Y ➞ Replace.
Correct connection wires
between indoor and
outdoor units.
Defective outdoor unit
control PCB ➞ Replace.
Defective connection wire.
(Broken)
Noise.
Defective indoor unit
control PCB ➞ Replace.