Mitsubishi Heavy Industries V Multi FDC71VNX Technical Manual page 164

Inverter packaged air conditioner
Hide thumbs Also See for V Multi FDC71VNX:
Table of Contents

Advertisement

Models FDC200, 250VSA
(1) Control PCB
Switch
SW1
Pump down operation
JSW1-1
JSW1-2
Model selection
JSW1-3
JSW1-4
SW3-1
Defrost condition
Snow protection control
SW3-2
Test run SW
SW3-3
SW3-4
Test run mode
Model selection
SW4-1
SW4-2
Model selection
Reserved
SW4-3
Reserved
SW4-4
SW5-1
Utilization of existing piping control
Reserved
SW5-2
Reserved
SW5-3
SW5-4
Reserved
SW7-1
Silent mode setting
Reserved
SW7-2
Anti frost control
SW7-3
Table 1: Outdoor unit model selection with JSW1-1-JSW1-4 and SW4-1-SW4-2
Switch
FDC200 FDC250
JSW1-1
ON
OFF
JSW1-2
ON
OFF
JSW1-3
OFF
ON
JSW1-4
OFF
OFF
SW4-1
ON
ON
SW4-2
OFF
OFF
(2) Inverter PCB
Switch
FDC200
JSW10-1
OFF
JSW10-2
OFF
JSW10-3
OFF
JSW10-4
OFF
JSW11-1
OFF
JSW11-2
OFF
JSW11-3
OFF
JSW11-4
OFF
* When checking inverter PCB of FDC200, 250 models with inverter checker, turn JSW10-4 ON.
(Regarding the checking method of inverter PCB with inverter checker, refer to page 158, 159 for details)
Description
Normal*/Pump down
Normal*/Cold region
Normal*/Snow protection
Normal*/Test run
Cooling*/Heating
Domestic/Overseas*
3 phase/Single phase
Normal*/Existing piping control
Capacity priority/Silent priority
Invalid/Valid
FDC250
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
163
-
-
'19 • PAC-T-327
Default setting
OFF
Normal
As per model
See table 1
OFF
Normal
Normal
OFF
Normal
OFF
OFF
Cooling
Overseas
See table 1
ON
As per model
See table 1
Keep OFF
OFF
Keep OFF
OFF
OFF
Keep OFF
Keep OFF
OFF
Keep OFF
OFF
OFF
Keep OFF
Silent priority
ON
Keep ON
ON
Valid
ON
* Default setting
Remark