Mitsubishi Heavy Industries V Multi FDC71VNX Technical Manual page 249

Inverter packaged air conditioner
Hide thumbs Also See for V Multi FDC71VNX:
Table of Contents

Advertisement

Error code
Indoor display
Remote control:
E59
Outdoor unit
Outdoor unit
inverter PCB
1. Applicable model
Models FDC100-140VNA/VSA
2. Error detection method
When it fails to change over to
the operation for rotor position
detection of compressor motor
3. Condition of error displayed
If the compressor fails to startup
for 20 times (10 patterns x2
times) continuously.
4. Presumable cause
• Faulty outdoor fan motor
• Faulty outdoor unit main PCB
• Anomalous power source
voltage
• Insufficient or excessive
refrigerant amount
• Faulty component for
refrigerant circuit
• Compressor anomaly
(Motor or bearing)
Note: Insulation resistance
• The unit is left for long period without power source or soon after installation, insulation resistance may decrease to several MΩ or lower due to the liquid refrigerant
migrated in the refrigerant oil in compressor. If the electric leakage breaker is activated due to low insulation resistance, check followings.
➀ Check whether the insulation resistance can recover or not, after 6 hours has passed since power ON.
(By energize the crankcase heater, liquid refrigerant migrated in the refrigerant oil in compressor can be evaporated.)
➁ C heck whether the electric leakage breaker conforms to high-harmonic specifications.
(As INVERTER PAC units has inverter, in order to prevent from improper operation, be sure to use the breaker of high-harmonic type.)
RUN light
Green LED
Keeps flashing
control PCB
Yellow LED
Stays OFF
5. Troubleshooting
In case that the compressor
does not start at all and no
sound or vibration exists
power source voltage
For
FDC100-140VSA
pressure equalized
at starting OK?
resistance and resistance
between terminals(1) of
TIMER light
Content
Compressor startup failure (1/2)
Red LED
5-time flash
(Models FDC100-140VN A/VSA only)
Diagnosis
Is
OK?
For
YES
FDC100-140VNA
Is DC15V
detected after disconnecting
outdoor fan motor?
NO
Replace outdoor unit main PCB
Can compressor startup?
NO
Is the
YES
Is the insulation
compressor OK?
(1) 0.448Ω or more at 20°C (Models FDC100-140VNA)
1.044Ω or more at 20°C (Models FDC100-140VSA)
YES
To next page
248
-
-
'19 • PAC-T-327
Countermeasure
Check the power source
NO
voltage and correct it.
Replace outdoor fan motor.
YES
OK
YES
Check refrigerant amount
NO
and refrigerant circuit.
Replace compressor.
NO