Mitsubishi Heavy Industries V Multi FDC71VNX Technical Manual page 165

Inverter packaged air conditioner
Hide thumbs Also See for V Multi FDC71VNX:
Table of Contents

Advertisement

(5) Check of anomalous operation data with the remote control
(a) In case of RC-EX3A remote control
[Operating procedure]
➀ On the TOP screen, touch the buttons in the order of "Menu" ➝ "Service setting" ➝ "Service & Maintenance" ➝
"Service password" ➝ "Set" ➝ "Error display" ➝ "Error history".
➁ When only one indoor unit is connected to the remote control, followings will be displayed.
1. When there is any anomaly: "Loading. Wait a while" is displayed, followed by the operation data at the occurrence
of anomaly
Contents of display
・ Error code
・ Number and data item
2. When there is no anomaly: "No anomaly" is displayed, and this mode is terminated.
➂ When two or more indoor units are connected to the remote control, followings will be displayed.
1. When there is any anomaly: If the unit having anomaly is selected on the "Select IU" screen, "Loading. Wait a while"
is displayed, followed by the operation data at the occurrence of anomaly.
Contents of display
・ Indoor unit No.
・ Error code
・ Number and data item
2. When there is no anomaly: "No anomaly" is displayed, ant this mode is terminated.
Note (1) When the number of connected units cannot be shown in a page, select "Next".
➃ If you press [RUN/STOP] button, the display returns to the TOP screen.
◎ If you touch "Back" button on the way of setting, the display returns to the last precious screen.
Note (1) When two remote controls are used to control indoor units, the check of anomaly operation data can be made on the master remote control only. (It
cannot be operated from the slave remote control.)
■ Anomaly operation data (Corresponding data may not be provided depending on models. Such items will not be displayed.)
Number
01
02
03
04
05
06
07
08
09
10
11
12
13
21
22
23
24
25
26
Details of compressor protection status No. 33
27
Models FDC71, 100, 125, 140VNX, 100, 125, 140VSX
28
Contents of display
29
Normal
30
Discharge pipe temperature protection control
31
Discharge pipe temperature anomaly
32
Current safe control of inverter primary current
33
High pressure protection control
34
High pressure anomaly
35
Low pressure protection control
36
Low pressure anomaly
37
Anti-frost prevention control
38
Current cut
39
Data Item
(Operation Mode)
(Set Temperature)
(Return Air Temperature)
(Remote Control Temperature Sensor)
(Indoor Heat Exchanger Temperature Sensor / U Bend)
(Indoor Heat Exchanger Temperature Sensor /Capillary)
(Indoor Heat Exchanger Temperature Sensor /Gas Header)
(Indoor Unit Fan Speed)
(Frequency Requirements)
(Response Frequency)
(Pulse of Indoor Unit Expansion Value)
(Total Running Hours of The Indoor Unit)
(Supply Air Temperature)
(Outdoor Air Temperature)
(Outdoor Heat Exchanger Temperature Sensor)
(Outdoor Heat Exchanger Temperature Sensor)
(Compressor Frequency)
(High Pressure)
(Low Pressure)
(Discharge Pipe Temperature)
(Comp Bottom Temperature)
Reference page
(Current)
(Target Super Heat)
P.128
.(a).(i)
(Super Heat)
P.128
.(a).(ii)
(Discharge Pipe Super Heat)
P.130
.(g)
(Protection State No. of The Compressor)
P.128
.(b).(i) P.39
.(c).(i)
(Outdoor Unit Fan Speed)
P.128
.(b).(ii)
(63H1 On/Off)
P.129
.(e).(i)
(Defrost Control On/Off)
P.129
.(e).(ii)
(Total Running Hours of The Compressor)
P.130
.(k)
(Pulse of The Outdoor Unit Expansion Valve EEVC)
P.130
.(g)
(Pulse of The Outdoor Unit Expansion Valve EEVH)
P.130
.(h)
P.130
.(i)
P.129
.(f)
P.131
.(l)
P.130
.(g)
P.131
.(p)
Details of compressor protection status No. 33
Models FDC71, 100, 125, 140VNX, 100, 125, 140VSX
No.
Contents of display
"0"
Normal
"1"
Discharge pipe temperature protection control
"2"
Discharge pipe temperature anomaly
"3"
Current safe control of inverter primary current
"4"
High pressure protection control
"5"
High pressure anomaly
"6"
Low pressure protection control
"7"
Low pressure anomaly
"8"
Anti-frost prevention control
"9"
Current cut
"10" Power transistor protection control
"11" Power transistor anomaly (Overheat)
"12" Compression ratio control
"13" Spare
"14" Dewing prevention control
"15" Current safe control of inverter secondary current
"16" Stop by compressor rotor lock
"17" Stop by compressor startup failure
"18" Active filter anomaly
Note(1) Operation data display on the remote control.
Data is dispalyed until canceling the protection control.
In case of multiple protections controlled, only the younger No. is displayed.
Note(2) Common item.
In heating mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "4" is displayed.
In cooling and dehumidifying mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "8" is displayed.
164
-
-
'19 • PAC-T-327
Reference page
P.128
.(a).(i)
P.128
.(a).(ii)
P.130
.(g)
P.128
.(b).(i) P.39
.(c).(i)
P.128
.(b).(ii)
P.129
.(e).(i)
P.129
.(e).(ii)
P.130
.(k)
P.130
.(g)
P.130
.(h)
P.130
.(i)
P.129
.(f)
P.131
.(l)
P.130
.(g)
P.131
.(p)
Note(1) Operation data displa
Data is dispalyed unti
In case of multiple pr
Note(2) Common item.
In heating mode.
During protection co
frequency from indo
In cooling and dehu
During protection co
frequency from indo