Preset point of the protective devices
Parts name
Temperature sensor
(for protection over-
loading in heating)
Temperature sensor
(for frost prevention)
Temperature sensor
(for protection high
pressure in cooling.)
Temperature sensor
(for detecting dis-
charge pipe temp.)
High pressure switch
(for protection)
Low pressure sensor
(for protection)
Equipped
Mark
unit
Th i -R
Indoor unit
Th i -R
Tho-R
Outdoor unit
Tho-D
Outdoor unit
63H1
Outdoor unit
LPT
Outdoor unit
FDT100, 125, 140 model
OFF 63˚C
OFF 1.0˚C
OFF 51˚C
OFF 115˚C
ON 85˚C
OFF 4.15MPa
ON 3.15MPa
OFF 0.227MPa
ON 0.079MPa
290
-
-
'19 • PAC-T-327
FDT200, 250 model
ON 56˚C
ON 10˚C
ON 65˚C
OFF 135˚C
ON 90˚C