3.2.2 SPECIFICATIONS

(1) Indoor units

Item
Power source
Sound power level
Operation
Sound pressure level
data
Silent mode sound pressure level
Exterior dimensions (Height × Width × Depth)
Exterior appearance
( Munsell color )
Net weight
Heat exchanger
Fan type & Q'ty
Fan motor (Starting method)
Air flow
Available external static pressure
Outside air intake
Air filter, Quality / Quantity
Shock & vibration absorber
Electric heater
Remote control
Operation
Room temperature control
control
Operation display
Safety equipments
Refrigerant piping size ( O.D. )
Installation
Connecting method
Attached length of piping
data
Insulation for piping
Drain hose
Drain pump, max lift height
IP number
Standard accessories
Option parts
Notes
(1) The data are measured at the following conditions.
Item
Indoor air temperature
DB
Operation
Cooling
27˚C
Heating
20˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.
(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
Model
Cooling
Heating
Cooling
dB(A)
Heating
mm
kg
W
Cooling
3
m
/min
Heating
Pa
W
(Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2
mm
m
mm
Outdoor air temperature
WB
DB
19˚C
35˚C
7˚C
-
FDT50VH
1 Phase 220-240V 50Hz / 220V 60Hz
55
56
P-Hi : 41 Hi : 33 Me : 30 Lo : 26
P-Hi : 42 Hi : 33 Me : 28 Lo : 20
Unit 236 × 840 × 840
Panel 35 × 950 × 950
Plaster white
( 6.8Y8.9/0.2 ) near equivalent
Unit 19
Panel 5
Louver fin & inner grooved tubing
Turbo fan ×1
50 < Direct line start >
P-Hi : 22 Hi : 16 Me : 13 Lo : 10
0
Possible
Pocket plastic net ×1 (Washable)
Rubber sleeve (for fan motor)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat.
Liquid line: ø 6.35 (1/4")
Gas line: ø 12.7 (1/2")
Flare piping
Necessary (both Liquid & Gas lines)
Hose connectable VP25 (O.D.32)
Built-in drain pump, 850
IPX0
Mounting kit, Drain hose
Standards
WB
24˚C
ISO5151-T1
6˚C
379
-
'19 • PAC-T-327
The pipe length is 7.5m.