Models FDC100, 125, 140VNA, 100, 125, 140VSA
No.
Contents of display
"0"
Normal
"1"
Discharge pipe temperature protection control
"2"
Discharge pipe temperature anomaly
"3"
Current safe control of inverter primary current
"4"
High pressure protection control
"5"
High pressure anomaly
"8"
Anti-frost prevention control
"9"
Current cut
"11" Power transistor anomaly (Overheat)
"12" Compression ratio control
"13" Spare
"14" Dewing prevention control
"15" Current safe control of inverter secondary current
"16" Stop by compressor rotor lock
"17" Stop by compressor startup failure
"18" Active filter anomaly
Models FDC200, 250VSA
No.
Contents of display
"0"
Normal
"1"
Discharge pipe temperature protection control
"2"
Discharge pipe temperature anomaly
"3"
Current safe control of inverter primary current
"4"
High pressure protection control
"5"
High pressure anomaly
"6"
Low pressure protection control
"7"
Low pressure anomaly
"8"
Anti-frost prevention control
"9"
Current cut
"10" Power transistor protection control
"11" Power transistor anomaly (Overheat)
"12" Compression ratio control
"13" Spare
"14" Dewing prevention control
"15" Current safe control of inverter secondary current
"16" Stop by compressor rotor lock
"17" Stop by compressor startup failure
"18" Active filter anomaly
Reference page
P.329
.(a).(i)
P.329
.(a).(ii)
P.330
.(f )
P.329
.(b).(i) (c).(i)
P.329
.(b).(ii)
P.331
.( j)
P.330
.(f )
P.331
.(h)
P.330
.(e)
P.331
.(k)
P.330
.(f )
P.332
.(o)
Reference page
P.339
.(a).(i)
P.339
.(a).(ii)
P.341
.(g)
P.339
.(b).(i) P.199
.(c).(i)
P.339
.(b).(ii)
P.340
.(e).(i)
P.340
.(e).(ii)
P.341
.(k)
P.341
.(g)
P.341
.(h)
P.341
.(i)
P.340
.(f )
P.342
.(1)
P.341
.(g)
P.342
.(p)
165
-
-
Note(1) Operation data display on the remote control.
Data is dispalyed until canceling the protection control.
In case of multiple protections controlled, only the younger No. is displayed.
Note(2) Common item.
In heating mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "4" is displayed.
In cooling and dehumidifying mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "8" is displayed.
Note(1) Operation data display on the remote control.
Data is dispalyed until canceling the protection control.
In case of multiple protections controlled, only the younger No. is displayed.
Note(2) Common item.
In heating mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "4" is displayed.
In cooling and dehumidifying mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "8" is displayed.