Mitsubishi Heavy Industries V Multi FDC71VNX Technical Manual page 375

Inverter packaged air conditioner
Hide thumbs Also See for V Multi FDC71VNX:
Table of Contents

Advertisement

[Example]
(Conditions)
Operation voltage ········ Indoor unit: 220V, 50Hz
Operation mode ··········· Cooling and Heating
Unit······························· Outdoor unit: FDC125VSX × 1 unit
Operation characteristics of each unit
Model
Item
Power consumption (kW)
Running current (A)
Total power consumption (kW)
(Cooling) 3.11 + 0.07 × 2 = 3.25 (kW)
(Heating) 3.26 + 0.07 × 2 = 3.4 (kW)
Total running current (A)
[
(Cooling) 7.9 +
(0.62 + 0.62 × )
[
(Heating) 8.2 +
(0.62+ 0.62×
Total power factor (%)
3.25 × 1000
(Cooling)
3 × 8.3 × 380
3.4 × 1000
(Heating)
3 × 8.6 × 380
Outdoor unit: 380V, 50Hz
Indoor unit: FDT60VH × 2 units
FDC125VSX
3.11/3.26
7.9/8.2
]
1
.
= 8.3 (A)
.
3
1
]
.
)
= 8.6 (A)
.
3
.
× 100 = 59 %
.
.
× 100 = 60 %
.
-
(Cooling/Heating)
FDT60VH
0.07/0.07
0.62/0.62
374
-
'19 • PAC-T-327

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents