Mitsubishi Heavy Industries V Multi FDC71VNX Technical Manual page 413

Inverter packaged air conditioner
Hide thumbs Also See for V Multi FDC71VNX:
Table of Contents

Advertisement

7. How to set functions by button operation
⑴   S top air-conditioner, and simultaneously press AIR CON No. and
at the same time for over three seconds.
  The function number "01" blinks in the upper right.
⑵ Press TEMP△ or TEMP▽ button.
  Select the function number.
MODE button.
⑶ Press
  Decide the function number.
⑷ [In the case of selecting the remote control function (01-06)]
① The current setting number of the selected function number blinks
   (Example)
    Function number: "01" (lighting)
    Setting number: "01" (blinking)
② Press TEMP△ or TEMP▽ button.
  Select the setting number.
MODE button.
③ Press
  The setting is completed.
    L ight is on for approximately 3 to 20 seconds while data of the
decided function No. and setting No. is transmitted.
 (Example)
   Function number: "01" (lighting for 3 to 20 seconds)
   Setting number: "01" (lighting for 3 to 20 seconds)
   T hen, the screen goes back to the function number blinking
indication ⑴ , if the setting is sequentially conducted, continue
with the same procedures. If the setting is finished, proceed to ⑸ .
⑸ Press
ON/OFF button.
  The setting is completed.
ON/OFF button is pressed during setting, the setting is ended. However, any details where the setting has not been completed will be ineffective.
・Even if
・The setting contents are stored in the control, and even if the power failure occur, this will not be lost.
[Confirmation method for current setting]
According to the operation, the "setting number" displayed first after selecting "function number" and pressing
(However, in the case of selecting "U ALL" (all units), the setting number of the lowest number among the indoor units is displayed.)
"88" blinks on the temperature setting indicator. (blinking for approximately 2 to 10 seconds while
data is read) Then, the return air temperature is displayed. When AIR CON No. is pressed, return
to the indoor unit selection display (example, "U 000").
ON/OFF button.
⑷ Press
End.
MODE buttons
Function number
[In the case of selecting the indoor unit function (07-14)]
① "88" blinks on the temperature setting indicators.
(blinking for approximately 2 to 10 seconds while data are read)
          ↓       
After that, the current setting number of the selected function number blinks.
  (Example)
Function number
Setting number
 Proceed to ② .
[Note]
a.   I n the case of connecting one remote control to plural indoor units, the display
   Indoor unit No. display: "U 000" (blinking)
   (Display the lowest number among the connected indoor units.)
Function number
Setting number
b.   P ress TEMP△ or TEMP▽ button.
c.   P ress
② Press TEMP△ or TEMP▽ button.
③ Press
 
-
Decide button
Start button
Function number: "07" (lighting)
Setting number: "01" (blinking)
will be as follows:
Indoor unit No.
Select the indoor unit No. to be set.
If "U ALL" is selected, the same setting can be set to all units.
MODE button.
Decide the indoor unit No.
"88" blinks on the temperature setting indicators. (blinking for 2 to 10 seconds while data
is read)
AIR CON No.
When
button is pressed, go back to the indoor unit selection display (for
example, "U 000" blinking).
Select the setting number
MODE button.
The setting is completed.
Light is on for approximately 3 to 20 seconds while data of the decided function No. and
setting No. is transmitted.
(Example)
Indoor unit No.: "U 000" (lighting for 3 to 20 seconds)
Function number: "07" (lighting for 3 to 20 seconds)
Setting number: "01" (lighting for 3 to 20 seconds)
Indoor unit No.
(In the case of
connecting
plural indoor
units)
Then, the screen goes back to the function number blinking indication ⑴ , if the setting
is sequentially conducted, continue with the same procedures. If the setting is finished,
proceed to ⑸ .
MODE button is the currently set content.
412
-
'19 • PAC-T-327
End button
Select button
Function number
Setting number
Function number
Function number
Setting number

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents