Item
Power source
Nominal cooling capacity (range)
Nominal heating capacity (range)
Power consumption
Max power consumption
Running current
Inrush current, max current
Operation
data
Power factor
EER
COP
Sound power level
Sound pressure level
Silent mode sound pressure level
Exterior dimensions (Height x Width x Depth)
Exterior appearance
( Munsell color )
Net weight
Compressor type & Q'ty
Compressor motor (Starting method)
Refrigerant oil (Amount, type)
Refrigerant (Type, amount, pre-charge length)
Heat exchanger
Refrigerant control
Fan type & Q'ty
Fan motor (Starting method)
Air flow
Available external static pressure
Outside air intake
Air filter, Quality / Quantity
Shock & vibration absorber
Electric heater
Remote control
Operation
Room temperature control
control
Operation display
Safety equipments
Refrigerant piping size ( O.D. )
Connecting method
Attached length of piping
Installation
data
Insulation for piping
Refrigerant line (one way) length
Vertical height diff. between O/U and I/U
Drain hose
Drain pump, max lift height
Recommended breaker size
L.R.A. (Locked rotor ampere)
Interconnecting wires
Size x Core number
IP number
Standard accessories
Option parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
DB
Operation
Cooling
27˚C
Heating
20˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
Model
Indoor unit FDT50VH
kW
kW
Cooling
Heating
kW
Cooling
Heating
A
Cooling
%
Heating
Cooling
Heating
Cooling
Heating
Cooling
dB(A)
P-Hi: 41 Hi: 33 Me: 30 Lo: 26
Heating
P-Hi: 42 Hi: 33 Me: 28 Lo: 20
Unit 236 x 840 x 840
mm
Panel 35 x 950 x 950
( 6.8Y8.9/0.2 ) near equivalent
kg
kW
kg
Louver fin & inner grooved tubing
W
50 < Direct line start >
Cooling
3
m
/min
P-Hi: 22 Hi: 16 Me: 13 Lo: 10
Heating
Pa
Pocket plastic net x 1 (Washable)
Rubber sleeve (for fan motor)
W
(Option) Wired : RC-EX3A, RC-E5, RCH-E3 Wireless : RCN-T-5AW-E2
Liquid line : I/U φ 6.35 (1/4") Pipe φ 6.35(1/4") x 0.8 O/U φ 6.35 (1/4")
mm
m
m
m
Max.20m (Outdoor unit is higher)
Hose connectable VP25(O.D.32)
mm
Built-in drain pump , 850
A
A
1.5mm
Mounting kit, Drain hose
Outdoor air temperature
WB
DB
19˚C
35˚C
24˚C
7˚C
-
FDT50ZSXVH
1 Phase, 220-240V 50Hz / 220V 60Hz
5.0 [ 1.1(Min.) - 5.6(Max.)]
5.4 [ 0.6(Min.) - 6.3(Max.)]
1.29
1.31
2.90
5.9 / 6.2
6.0 / 6.3
5, 15
95
95
3.88
4.12
55
56
Plaster white
Unit 19 Panel 5
R410A 1.5kg in outdoor unit (Incl. the amount for the piping of : 15m)
Capillary tubes + Electronic expansion valve
Turbo fan x 1
0
Possible
0
Thermostat by electronics
Overload protection for fan motor
Frost protection thermostat
Internal thermostat for fan motor
Abnormal discharge temperature protection
Gas line : φ 12.7 (1/2") φ 12.7(1/2") x 0.8 φ 12.7 (1/2")
Flare piping
Necessary (both Liquid & Gas lines)
Max.30m
5.0
2
x 4 cores (Including earth cable) / Terminal block (Screw fixing type)
IPX0
Standards
WB
ISO5151-H1
6˚C
6
-
'19 • PAC-T-327
Outdoor unit SRC50ZSX-S
63
50
49
Cooling : 42 / Heating : 43
640 x 800 (+71) x 290
Stucco white
Munsell : ( 4.2Y7.5/1.1 ), RAL : 7044
45
RMT5113MCE2 ( Twin rotary type ) x 1
Direct line start
0.45 (MA68)
M shape fin & inner grooved tubing
Propeller fan x 1
34 < Direct line start >
39
33
0
Rubber sleeve (for compressor)
Flare piping
Max.20m (Outdoor unit is lower)
Hole size φ 20 x 5pcs
IPX4
Drain elbow, Drain hole grommet
The pipe length is 7.5m.
PJF000Z551
A