Mounting Dimensions, Clearances, And Assembly Type - Siemens SIRIUS 3RW30 Manual

Industrial controls
Hide thumbs Also See for SIRIUS 3RW30:
Table of Contents

Advertisement

Installation
8.1 Installing the soft starter
8.1.3

Mounting dimensions, clearances, and assembly type

The minimum clearances from other devices must be complied with to ensure unobstructed
cooling as well as the free supply and discharge of air to and from the heat sink.
Figure 8-1
Article No.
3RW301./3RW302.
3RW303./3RW304
3RW402.
3RW403./3RW404.
3RW405./3RW407.
Note
Allow sufficient clearances for the cooling air to circulate freely. The device is ventilated from
bottom to top.
68
Clearances from other devices
a (mm)
15
30
15
30
5
a (in)
b (mm)
0.59
60
1.18
60
0.59
60
1.18
60
0.2
100
Manual, 10/2018, NEB535199502000/RS-AB/005
b (in)
c (mm)
c (in)
2.36
40
1.56
2.36
40
1.56
2.36
40
1.56
2.36
40
1.56
4
75
3
SIRIUS 3RW30 / 3RW40

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirius 3rw40

Table of Contents