Stopping Operation; Protective Functions - Shindaiwa DG150MM Owners And Operation Manual

Diesel engine generator
Table of Contents

Advertisement

9-3. Stopping Operation

CAUTION : BURNS
 Do not touch the engine and surrounding components immediately after
stopping the engine as they are still hot.
Turn the switches and breakers on the load side to "OFF".
1
Turn the circuit breaker on the operation panel to "OFF".
2
Set the throttle lever to "IDLING".
3
4
The engine cools down for approximately 3 minutes.
Turn the starter switch to "STOP".
5

9-4. Protective Functions

WARNING : INJURY
 Do not open the check door during operation. Be careful of pinching or
catching of moving parts such as the cooling fan and fan belt.
 Always be sure to stop the engine and remove the
performing inspection or maintenance.
CAUTION : BURNS
 Do not open the check door during operation. Keep away from moving parts
such as cooling fan and fan belt.
 Hot steam gushes out from the coolant subtank if the generator overheats.
Do not touch the coolant subtank.
This generator is equipped with functions to automatically stop operation when there
is a fault/malfunction during operation, and one to warn the operator of the fault
location by use of indicator lamps. Check the fault location when the engine is
automatically stopped or an indicator lamp lights up to stop the engine.
Protection Feature List
Action
No.
Abnormality
High Water
1
Temperature
Low Oil
2
Pressure
Battery
3
Charge
Insufficient
Air Filter
4
Clogging Up
Water
5
Separator
Fluid Level
6
Current Leakage
7
Overload
*  indicates the automatic activation.
Earth
Engine
Leakage
Breaker
Automatic
Relay
Trip
Shutdown
Active
28
starter
Warning
Indicator
Blinking.
Activates due to high water temperature
in the engine. Default 100°C
Activate due to low oil pressure in the
engine. Default 0.98  100 kPa
Activates in battery charge Impossible.
The element is clogged making it
necessary to clean or replace the
element.
When the water separator is full of
water.
Activates in current leakage.
Activates in overload.
Flashes when at approx 80% of rated
output.
Load rejection when the rated output is
exceeded.
key when
Cause