Procedures During Operation - Shindaiwa DG150MM Owners And Operation Manual

Diesel engine generator
Table of Contents

Advertisement

9-2. Procedures during Operation

(1) Checks after Startup
 Make sure that all meters and indicators are in normal status. ( Ref. "5. Equipment")
 Check that there is no abnormal vibration or noise.
 Check that the exhaust gas color is normal. When operation is normal, the exhaust gas
should be colorless or slightly bluish.
< Note >
 If abnormal, stop using this generator and request authorized distributor where the
generator was purchased to repair the generator.
(2) Adjustment during Operation
During load operation, check the voltmeter and finely adjust voltage using the
voltage regulator dial.
 Bleeding air from the fuel system when the engine stops due to running out
of fuel
If air enters the fuel system, it must be expelled in accordance with the following
procedure before the engine can be started. It is not sufficient only to fill the fuel
tank.
Refuel.
1
Turn the starter switch to "RUN" and activate the
2
electromagnetic pump. Do not turn the starter key to
"START" and start the engine.
Loosen the air bleed plug mounted the fuel filter.
3
Cover the the air bleed plug with a soft cloth.
Tighten the air bleed plug after babbles are not
4
confirmed visually.
Air bleeder plug tightening torque
8 ~ 12 N・m(0.8 ~ 1.2 kgf・m)
Do not overtorque the air bleed plug.
5
Wipe and clean if it spilled fuel.
Set the throttle lever to "IDLING". Start the engine. Repeat the stop #3 if the
6
engine did not start.
Start the engine and check that the air is bled off completely from the fuel system.
7
The fuel injection pump will be air-bled automatically when the engine is started.
Make sure that there is no leaking the fuel from the seal point.
8
27
Air bleed plug
Fuel Filter
(Main)

Advertisement

Table of Contents
loading