Stopping Operation; Protective Functions - Shindaiwa DG37MK-P Owner's And Operator's Manual

Diesel engine generator
Table of Contents

Advertisement

< Note >
 Turn the throttle switch to IDLING, start the engine and check that the air is completely bled from
the system. If air bleeding is not complete, engine rotation will not be stable. In that case, repeat
the air bleeding operation.

9-3. Stopping Operation

CAUTION : BURNS
 Do not touch the engine and surrounding components immediately after
stopping the engine as they are still hot.
Turn the switches and breakers on the load side to OFF.
1
Turn the main breaker on the operation panel to OFF.
2
Turn the Throttle switch to IDLING.
3
The engine cools down for approximately three minutes.
4
Turn the starter switch to STOP.
5

9-4. Protective Functions

WARNING : INJURY
 Do not open the check door during operation. Be careful of pinching or
catching of moving parts such as the cooling fan and fan belt.
 Always be sure to stop the engine and remove the engine key when
performing inspection or maintenance.
CAUTION : BURNS
 Do not touch the engine and surrounding components immediately after
stopping the engine as they are still hot.
 Hot steam gushes out from the coolant subtank if the generator overheats.
Do not touch the coolant subtank.
This generator is equipped with functions to automatically stop operation when there is a
fault/malfunction during operation, and one to warn the operator of the fault location by use
of indicator lamps. Check the fault location when the engine is automatically stopped or an
indicator lamp lights up to stop the engine.