9-2. Procedures during Operation

(1) Checks after Startup
 Make sure that all meters and indicators are in normal status. (Refer to section "5. Equipment".)
 Check that there is no abnormal vibration or noise.
 Check that the exhaust gas color is normal. When operation is normal, the exhaust gas should
be colorless or slightly bluish.
< Note >
 If abnormal, stop using this generator and request authorized distributor where the generator was
purchased to repair the generator.
(2) Adjustment during Operation
During load operation, check the voltmeter and finely adjust voltage using the voltage
regulator dial.
 Bleeding air from the fuel system when the engine stops due to running out of fuel
This generator is equipped with an automatic air bleeding mechanism. Perform the
following procedures when the engine stops due to running out of fuel to easily bleed
the air from the system.
Add fuel to the generator.
1
Turn the starter switch to RUN. Air bleeding is completed approximately in 2 minutes.
2
< Note >
 Set the throttle lever to IDLING, start the engine and check that the air is completely bled from the
system. If air bleeding is not complete, engine rotation will not be stable. In that case, repeat the
air bleeding operation.

9-3. Stopping Operation

CAUTION : BURNS
 Do not touch the engine and surrounding components immediately after
stopping the engine as they are still hot.
Turn the switches and breakers on the load side to OFF.
1
Turn the circuit breaker for 3-phase and 1-phase to OFF.
2
Set the throttle lever to IDLING.
3
The engine cools down for approximately 3 minutes.
4
Turn the starter switch to STOP.
5
29