9-3. Procedures during Operation

(1) Checks after Startup
Make sure that all meters and indicators are in normal status.
(Refer to section "5. Equipment")
Check that there is no abnormal vibration or noise.
Check that the exhaust gas color is normal. When operation is normal, the exhaust gas
should be colorless or slightly bluish.
< NOTE >
If abnormality is found, stop using this generator and request the authorized distributor
where the generator was purchased to repair the generator.
(2) Adjustment during Operation
During load operation, check the voltmeter and properly adjust the voltage using the
voltage regulator dial.
Bleeding air from the fuel system when the engine stops due to running out of fuel,
this generator is equipped with an automatic air bleeding mechanism. Perform the
following procedures when the engine stops to bleed the air automatically.
1
Add fuel to the generator.
Turn the starter switch will be RUN. Air bleeding is completed in approximately
2
30 seconds.
< NOTE >
Start the engine and check that the air is completely bled from the system. If air bleeding is
not complete, engine rotation will not be stable. In that case, repeat the air bleeding
operation.

9-4. Stopping Operation

CAUTION : BURNS
Do not touch the engine and surrounding components immediately after
stopping the equipment, while temperature can reach extremely high.
1
Turn the switches and breakers on the load side to OFF.
2
Turn the circuit breaker on the operation panel to OFF.
3
Turn the throttle switch to START position.
4
The engine cools down for approximately three minutes.
Turn the starter switch to STOP.
5
35