Stopping Operation - Shindaiwa DGK15FU Owner's And Operator's Manual

Diesel engine generator
Table of Contents

Advertisement

Set the STARTER SWITCH selector to "START," and confirm that the engine has started
4
properly.
The engine speed is unstable for approximately one minute until the air has been
5
completely pulled out from the fuel line. The engine speed stabilizes once the air is
pulled out.
< Note >
Do not apply any loads until air-bleeding has been completed (until the engine speed becomes
stable). Doing so can cause a malfunction.
If repeating STARTER SWITCH operation, wait 30 seconds or more between re-starting.
If the engine stops immediately after starting, the machine tries to restart it automatically.
If the over crank indicator lights up, return the STARTER SWITCH selector to the "STOP" position
first, and then set to "START" again.

9-3. Stopping Operation

CAUTION : BURNS
Do not touch the engine and surrounding components immediately after
stopping the engine as they are still extremely hot.
(1) Manual Start
1
Turn the switches and breakers on the load side to OFF.
2
Turn the three-phase and single-phase breakers on the operation panel to OFF.
Confirm that the accessory switch is set to "OFF."
3
The engine cools down for approximately 3 minutes.
4
Turn the STARTER SWITCH to STOP.
5
After the engine stops, turn the fuel lever to CLOSE.
6
< Note >
Never turn accessory switch ON during operation.The engine keeps running while accessory
switch is ON.
If the engine does not stop even if the STARTER SWITCH is set to "STOP", close the fuel
cock.The engine will stop after a few minutes. If this occurs, stop using the generator and have it
repaired by the authorized distributor where this generator was purchased.
Set the STARTER SWITCH selector to "STOP" if you do not plan to use the generator for a
prolonged period of time. If you leave the selector in the "AUTO" or "START" position, the standby
current may drain the battery.