Procedures During Operation; Stopping Operation - Shindaiwa DG60MI Owner's And Operator's Manual

Table of Contents

Advertisement

9-2. Procedures during Operation

(1) Checks after Startup
 Make sure that the controller and hour meter are in normal status. (Refer to section "5.
Equipment".)
 Check that there is no abnormal vibration or noise.
 Check that the exhaust gas color is normal. When operation is normal, the exhaust gas should
be colorless or slightly bluish.
< Note >
 If abnormal, stop using this generator and request authorized distributor where the generator
was purchased to repair the generator.
(2) Adjustment during Operation
During load operation, check the voltage on the Operation Display and finely adjust
voltage using the voltage regulator dial.
 Restarting after stopping due to running out of fuel.
The fuel filter includes an automatic air-bleeding device. Restart the engine according
to the following procedures even if the engine has stopped due to running out of fuel.
Add fuel to the generator.
1
Press and hold the Lamp Test / Air Bleeding Button for approximately 2 seconds to
2
automatically starts air-bleeding device.
Press the Manual Mode Button.
3
Press the Start Button, and confirm the engine has started properly.
4
< Note >
 Start the engine and check that the air is completely bled from the system. If air bleeding is not
complete, engine rotation will not be stable. In that case, repeat the air bleeding operation.

9-3. Stopping Operation

CAUTION : BURNS
 Do not touch the engine and surrounding components immediately after
stopping the engine as they are still extremely hot.
(1) Manual Start
Turn the switches and breakers on the load side to OFF position.
1
Turn the breaker on the operation panel to OFF position.
2
The engine cools down for approximately 3 minutes.
3
Press the Stop Mode Button to shut off the engine.
4
Turn the Power Switch to OFF position.
5
< Note >
 Set the Power Switch to OFF position if the generator will not be used for a prolonged period.
If you leave the Power Switch in the OFF position, the standby current may drain the battery.
(2) Auto Start
The engine stops when the RS1/RS2 terminals open.
1
Turn the breaker on the operation panel to OFF position.
2
Press the Stop Mode Button to shut off the engine.
3
Turn the Power Switch to OFF position.
4
A
ir-bleeding device runs for up to 4 minutes.
31

Advertisement

Table of Contents
loading

Table of Contents