Gas Line Requirements; Fuel; Gas Line Connection; Gas Inlet Pressure - FireplaceXtrordinair 4237 EG Installation Manual

Hide thumbs Also See for 4237 EG:
Table of Contents

Advertisement

18

Gas Line Requirements

MASSACHUSETTS INSTALLATIONS - WARNING:
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE
COMMONWEALTH OF MASSACHUSETTS.
OTHER MASSACHUSETTS CODE REQUIREMENTS:
Flexible connector must not be longer than 36 inches.
Shutoff valve must be a "T" handle gas cock.
Only direct vent sealed combustion products are approved for bedrooms or bathrooms.
Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas log.
A carbon monoxide (CO) detector is required in the same room as the appliance.
The gas line must be installed in accordance with all local codes and the requirements listed below.
In the absence of local codes, follow ANSI 223.1 in US/Canada or AS/NZS 5601.1 in Australia.
The fireplace and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPA). For pressures under
1/2 psig (3.5 kPA), isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
This unit has been listed using the included internal gas shutoff valve.

Fuel

This fireplace is designed either for natural gas or for propane (but not for both).

Gas Line Connection

Installation must be performed by a qualified installer, service agency, or the gas supplier (In Massachusetts a
licensed plumber/gasfitter).

Gas Inlet Pressure

If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately
adjusted, and the total gas load for the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or the propane tank) should supply
gas at the input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.

Gas Line Location

The gas line is located on the left side of the appliance in the location shown below. The gas inlet
accepts a 1/2" FPT.
© Travis Industries
Installation
(for qualified installers only)
Maximum Input Pressure
Natural Gas
Propane
9/22/2021 - 1561
Minimum Input Pressure
7" W.C. (1.74 kPA)
13" W.C. (3.23 kPA)
5.5" W.C. (1.37 kPA)
11" W.C. (2.74 kPA)
4237 EG