Appendix 1.5.2
CC-Link IE Field communication unit setup
To connect the communication unit to the CC-Link IE Field network, set the station number and the network number.
Ensure that these numbers are the same as configured on the CC-Link IE Field master/local module.
Figure 1.5.2-1: SC-HG1- CEF hardware setup
(1) Set the network number
By factory default, the network number of the communication unit is set to '01'. If you want to operate the product with a
different network number, use the following steps to change the network number.
With the communication unit powered OFF, turn ON the operating mode setting switch to turn ON the power.
Once you power ON the communication unit, the STS1 indicator (green) flashes to indicate that you are now in network
number setting mode. So operate the rotary switch to set the network number. The network number is configurable within
the range of 01 to EF in hexadecimal.
When you are done setting the network number, turn OFF the mode setting switch (SW1) to save the new network number
in the communication unit and check that the STS1 indicator (green) stays ON instead of flashing.
With the mode setting switch (SW1) OFF, turn OFF and back ON the power to start the CC-Link IE Field network
communication with the specified network number.
* Before turning back ON the power supply, set the station number by operating the rotary switch.
SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
WUME-SCHG1IQRFB-1
137/184