Panasonic SC-HG1 Series Reference Manual page 59

For mitsubishi melsec iq-r series sequencer
Table of Contents

Advertisement

Name
Hold Setting
i_uHoldSetting
Self Triger Level
i_dSelfTriggerLevel
Static Span
i_udStaticSpan
Self Delay Timer
i_uSelfDelayTimer
Variable name
Data type
Word
[Unsigned]
Double
word
[Signed]
Double
word
[Unsigned]
Word
[Unsigned]
SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
Valid range
bits 15 to 12
0 to 8
bits 11 to 8
0,1
bits 7 to 4
0,1
bits 3 to 0
0,1
-1999999 to 1999999
(decimal)
0 to 1999999 (decimal)
0 to 9999 (decimal)
59/184
Description
- Measurement mode (bits 15 to 12)
0 = Sample hold
1 = peak hold
2 = Bottom hold
3 = Peak-to-peak hold
4 = Peak-to-peak hold/2
5 = NG hold
6 = Self sample hold
7 = Self peak hold
8 = Self bottom hold
- Trigger mode (bits 11 to 8)
0 = One-shot
1 = Hold
- Self trigger edge direction (bits 7 to 4)
0 = Leading edge
1 = Trailing edge
- Self trigger delay (bits 3 to 0)
0 = Static span
1 = Delay timer
Setting Hold Setting (i_uHoldSetting) to
H6***, H7***, or H8*** requires you to
set the self trigger level.
The setting x 0.0001mm is applied to the
controller as the self trigger level.
Setting Hold Setting (i_uHoldSetting) to
H6**0, H7**0, or H8**0 requires you to
set the static span.
The setting x 0.0001mm is applied to the
controller as the static span.
Setting Hold Setting (i_uHoldSetting) to
H6**1, H7**1, or H8**1 requires you to
set the self delay timer. The setting unit
is [ms].
WUME-SCHG1IQRFB-1

Advertisement

Table of Contents
loading

Table of Contents