(2) Setting module parameters (when using the CC-Link master/local module)
Next, configure the module parameters.
Configure "CC-Link configuration" and "link refresh settings" under "basic settings".
Navigation window → Parameter → Module information → (Start XY): RJ61BT11 → Module parameter
Under "CC-Link configuration", set the communication unit to be connected.
You can also drag a " General Remote Device Station " from the module list at the right and down it onto the configuration
below.
At this time, you can restrict the setting items by using CSP+ of SC-HG1-C.
Ensure that the red-framed information you configure or check here is the same as configured on the communication unit.
The mode settings for SC-HG1-C are restricted depending on the operation mode you configure. Refer to the following
table to configure the settings.
CC-Link mode2 and CC-Link mode3 uses the extended cyclic function and therefore the mode setting does not work in
"Ver.1 mode".
Ver.1 mode
Ver.2 mode
Configure the values for setup items for each operation mode as instructed in the table below.
Number of occupied stations
Extended cyclic settings
Figure 1.5.3-5: Module parameters (basic settings)
CC-Link mode1
CC-Link mode1
Version
4-station occupied 2-station occupied 4-station occupied
SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
CC-Link mode2
×
CC-Link mode2
Ver.1
Ver.2
-
Eightfold setting
141/184
CC-Link mode3
×
CC-Link mode3
Ver.2
Fourfold setting
WUME-SCHG1IQRFB-1