Panasonic SC-HG1 Series Reference Manual page 148

For mitsubishi melsec iq-r series sequencer
Table of Contents

Advertisement

Under [Network Configuration Settings], set the communication unit to be connected.
You can also drag a "general-purpose remote device station" from the module list at the right and down it onto the
configuration below.
Next, configure the station number and the RX/RY and RWw/RWr settings.
Set the station number (enclosed in a red frame) to the station number used by the communication unit.
Set the RX/RY and RWw/RWr settings (enclosed in a blue frame) so that the number of points for the RX/RY settings are
128 and the number of points for the RWw/RWr settings 64.
Using SC-HG1-CEF's CSP+ at this time ensures that the number of points for the RX/RY and RWw/RWr settings are
entered. If you want to connect to multiple slave stations, configure them so that their ranges from the start to the end do
not overlap with each other.
Figure 1.5.4-7: Network configuration settings
Figure 1.5.4-8: Network configuration settings (when using CSP+)
SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
WUME-SCHG1IQRFB-1
148/184