Fitting The Burner (Gas Condensing Module); Checking The Neutralising System (If Installed); Yearly Maintenance Of Fuel Cell Module - Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

Commissioning, inspection, maintenance

Fitting the burner (gas condensing module)

4x
F
D
C
B
A
Fig. 76
1. Insert the burner and tighten screws
Torque: 6.5 Nm
2. Fit gas supply pipe
E
Torque: 30 Nm
3. Check the gas connections for leaks.
Danger
Escaping gas leads to a risk of explosion.
Check the fitting for gas tightness.

Checking the neutralising system (if installed)

5-yearly maintenance of fuel cell module

Note
Before carrying out the maintenance work:
The fuel cell module must be in maintenance mode.
Start maintenance mode, see page 72.
The distilled water must have been drained.
82
E
F
diagonally.
with a new gasket.
4. Connect the cables/leads:
Fan motor
A
Ionisation electrode
Ignition unit
C
Earth
D
B