Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors page 134

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

Troubleshooting
Fault messages on the gas condensing...
Control unit
System characteristics
message
F.524/18F1
No power generation
F.527
Burner locked out
F.528
Burner locked out
F.540
Burner in a fault state
F.542
Mixer closes. Heating circuit
pump is operational.
F.543
Mixer closes. Heating circuit
pump is operational.
F.544
Mixer closes. Heating circuit
pump is operational.
F.545
Mixer closes. Heating circuit
pump is operational.
F.546
Mixer closes. Heating circuit
pump is operational.
F.547
Mixer closes. Heating circuit
pump is operational.
F.548
Mixer closes. Heating circuit
pump is operational.
F.549
Mixer closes. Heating circuit
pump is operational.
Note
If subscriber faults occur, "Error, subscriber ..." is dis-
played.
134
(cont.)
Cause
Fault, reformer burner ig-
nition
Update parameters faulty
or incomplete
Basic programming faulty
or incomplete
Condensation water accu-
mulation in the heat cell
Lead break, flow tempera-
ture sensor, heating circuit
1 with mixer
Short circuit, flow temper-
ature sensor 1 in heating
circuit with mixer
Lead break, flow tempera-
ture sensor, heating circuit
2 with mixer
Short circuit, flow temper-
ature sensor 2 in heating
circuit with mixer
Lead break, flow tempera-
ture sensor, heating circuit
3 with mixer
Short circuit, flow temper-
ature sensor 3 in heating
circuit with mixer
Lead break, flow tempera-
ture sensor, heating circuit
4 with mixer
Short circuit, flow temper-
ature sensor 4 in heating
circuit with mixer
Measures
Reset the fault once.
If the fault recurs, notify Viessmann
Technical Service.
Repeat burner control unit flash
operation.
Repeat burner control unit flash
operation.
Check if condensate banked.
Check condensate drain and trap.
Note
To prevent water damage, detach
fan unit before removing the burn-
er.
Reset device.
Check flow temperature sensor
TS1 on extension kit mixer (elec-
tronics module ADIO). See
page 140.
Check flow temperature sensor
TS1 on extension kit mixer (elec-
tronics module ADIO). See
page 140.
Check flow temperature sensor
TS1 on extension kit mixer (elec-
tronics module ADIO). See
page 140.
Check flow temperature sensor
TS1 on extension kit mixer (elec-
tronics module ADIO). See
page 140.
Check flow temperature sensor
TS1 on extension kit mixer (elec-
tronics module ADIO). See
page 140.
Check flow temperature sensor
TS1 on extension kit mixer (elec-
tronics module ADIO). See
page 140.
Check flow temperature sensor
TS1 on extension kit mixer (elec-
tronics module ADIO). See
page 140.
Check flow temperature sensor
TS1 on extension kit mixer (elec-
tronics module ADIO). See
page 140.