Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors page 95

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

DHW
(cont.)
503.0 "Scald protection"
Setting
OFF
ON
534.0 "Circulation pump run-on"
Setting
120 s
1101.2 "Set speed of the primary circuit pump for DHW heating"
Setting
Explanations
The adjustable water temperature is limited to a maxi-
mum value.
0
Scald protection OFF
Danger
Risk of injury due to increased DHW tempera-
ture.
Inform the system user of the risk from the high-
er outlet temperature at the taps.
1
Scald protection ON (maximum DHW temperature 60
°C)
Note
Even with the scald protection switched on, higher
outlet temperatures may occur at the draw-off points
in the following cases:
With active hygiene function
While the appliance is being calibrated
Explanations
Circulation pump run-on after cylinder heating
120
Delivered condition 120 s run-on
0 to 900
Run-on time adjustable from 0 to 900 s in 60 s incre-
ments
Note
To avoid damaging the appliance, do not set the run-
on time to < 120 s.
Explanations
Set speed of the internal circulation pump when oper-
ated as a circulation pump for cylinder heating
...
Delivered condition specified by settings specific to
the appliance
20 to 100
Set speed adjustable from 20 to 100 %
System configuration (parameters)