Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors page 101

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

Heating circuit 1, Heating circuit 2, Heating...
1193.1 "Maximum flow temperature limit, heating circuit 2"
Setting
74 °C
1194.0 "Minimum flow temperature limit, heating circuit 3"
Setting
20 °C
1194.1 "Maximum flow temperature limit, heating circuit 3"
Setting
74 °C
1195.0 "Minimum flow temperature limit, heating circuit 4"
Setting
20 °C
1195.1 "Maximum flow temperature limit, heating circuit 4"
Setting
74 °C
1395.1 "Heating limit: Economy function, outside temperature, heating circuit 1"
Setting
25 °C
(cont.)
Explanations
Maximum flow temperature limit for the heating circuit
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters
Explanations
Minimum flow temperature limit for the heating circuit
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
Explanations
Maximum flow temperature limit for the heating circuit
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters
Explanations
Minimum flow temperature limit for the heating circuit
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
Explanations
Maximum flow temperature limit for the heating circuit
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters
Explanations
Heating circuit pump logic function (summer economy
control): Heating circuit pump switches off when out-
side temperature 1 K above selected value. Heating
circuit pump switches back on when outside tempera-
ture 1 K below selected value.
25
Delivered condition: Heating limit at outside tempera-
ture 25 °C
10 to 35
Heating limit adjustable from 10 to 35 °C in 1 °C incre-
ments
System configuration (parameters)
101

Advertisement

Table of Contents
loading

This manual is also suitable for:

F11tF19tF25tF32t

Table of Contents