Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors page 96

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

System configuration (parameters)
Heating circuit 1, Heating circuit 2, Heating circuit 3, Heating circuit 4
Note
Parameter values in bold are factory settings.
424.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 1"
Setting
0 K
424.4 "Duration for set flow temperature increase, heating circuit 1"
Setting
60 min
426.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 2"
Setting
0 K
426.4 "Duration for set flow temperature increase, heating circuit 2"
Setting
60 min
428.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 3"
Setting
0 K
96
Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0
Delivered condition increase 0 K
0 to 20
Temperature rise adjustable from 0 to 20 K
Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60
Delivered condition 60 min
0 to 120
Temperature rise adjustable from 0 to 120 min
Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0
Delivered condition increase 0 K
0 to 20
Temperature rise adjustable from 0 to 20 K
Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60
Delivered condition 60 min
0 to 120
Temperature rise adjustable from 0 to 120 min
Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0
Delivered condition increase 0 K
0 to 20
Temperature rise adjustable from 0 to 20 K

Advertisement