Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors page 123

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

Fault messages on the gas condensing...
Control unit
System characteristics
message
F.357
Burner in a fault state
F.359
Burner in a fault state
F.361
Burner in a fault state
F.365
Burner in a fault state
F.366
Burner in a fault state
F.367
Burner in a fault state
F.368
Burner locked out
(cont.)
Cause
Insufficient gas supply
No ignition spark
Flame signal is not
present or insufficient at
burner start.
Relay contact gas valve
feedback implausible
Gas valve electricity sup-
ply does not turn off.
Gas valve electricity sup-
ply does not turn off.
Gas pressure switch fault.
Forced ventilation time ex-
pired.
Troubleshooting
Measures
Check that the gas shut-off valve is
open.
Optically check input-side screen
in the gas train for contamination.
Test static gas pressure and gas
flow pressure. Check on-site gas
line and gas flow switch for correct
dimensioning.
Note
If the building pressure regulator
has a leak, you may notice rising
pressure when the burner is idle.
When the system is restarted, the
gas flow switch may trip.
Reset device.
Check connection and connecting
cables on ignition module and igni-
tion electrode.
Check for a voltage of 230 V at the
ignition module during the ignition
phase.
Check whether the ignition elec-
trode insulation is damaged.
Reset device.
Check ionisation electrode and
connecting cable. Check plug-in
connection for loose connections.
Note
Deposits on the electrodes indicate
foreign bodies in the combustion
air. Check the installation room and
flue system for causes of the de-
posits. For example: Laundry de-
tergents, cleaning agents, toilet-
ries, deposits in the ventilation air
supply (chimney).
Reset device.
Reset device.
Reset device.
Reset device.
Check gas supply (gas pres-
sure).
If available: Check gas pressure
switch for correct function.
If necessary, disconnect the gas
pressure switch connector and
check whether the burner starts.
123