System configuration (parameters)
Heating circuit 1, Heating circuit 2, Heating...
936.7 "Room influence factor, heating circuit 4"
Setting
1102.0 "Min. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1"
Setting
1102.1 "Max. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1"
Setting
1192.0 "Minimum flow temperature limit, heating circuit 1"
Setting
20 °C
1192.1 "Maximum flow temperature limit, heating circuit 1"
Setting
74 °C
1193.0 "Minimum flow temperature limit, heating circuit 2"
Setting
20 °C
100
(cont.)
Explanations
The higher the value, the greater the influence of the
room temperature on the set flow temperature of the
heating circuit (heating curve). Operation with room
temperature hook-up must be set for the heating cir-
cuit (parameter 936.6). Change value for heating cir-
cuit with mixer only.
For a sample calculation, see chapter "Heating curve"
in the "Function description"
8
Room influence factor
0 to 64
Room influence adjustable from 0 to 64
Explanations
Minimum speed of the internal circulation pump in
heating mode with standard room temperature
...
Delivered condition specified by settings specific to
the heat generator
0 to 100
Minimum speed adjustable from 0 to 100 %
Explanations
Maximum speed of the internal circulation pump in
heating mode with standard room temperature
...
Delivered condition specified by settings specific to
the heat generator
0 to 100
Maximum speed adjustable from 0 to 100 %
Explanations
Minimum flow temperature limit for the heating circuit
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
Explanations
Maximum flow temperature limit for the heating circuit
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters
Explanations
Minimum flow temperature limit for the heating circuit
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters