Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors page 122

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

Troubleshooting
Fault messages on the gas condensing...
Control unit
System characteristics
message
F.349
Control mode
Burner is operating with a
limited modulation range.
F.350
Burner in a fault state
F.351
Burner in a fault state
F.352
Burner in a fault state
F.353
Burner locked out
F.354
Burner in a fault state
F.355
Burner in a fault state
122
(cont.)
Cause
Air mass flow rate in fan
unit has not been correctly
recognised.
Ionisation voltage lies out-
side the permissible range
Ionisation current lies out-
side the permissible range
CO limit within appliance
exceeded
Insufficient gas supply,
burner output reduced
Gas modulation valve tol-
erance outside permissi-
ble range
Analogue signal reference
check: Flame signal is al-
ready present at burner
start.
Measures
Check mass flow sensor on the fan
unit. Check flue system for flue gas
congestion.
Check ionisation electrode and
connecting cable.
Reset device.
Check ionisation electrode and
connecting cable.
Reset device.
Check entire flue gas path for the
following:
Flue gas recirculation
Leak
Flue gas congestion caused by
water sack (if the flue gas system
is not steep enough)
Constriction
Blockage
Repair flue system if necessary.
Reset device.
Check the gas supply.
Optically check input-side screen
in the gas train for contamination.
Reset device.
Check connecting cable for gas
train for damage.
Check gas train.
Check the flue system for conges-
tion, constriction.
Reset device.
Check if condensate banked.
Note
To prevent water damage, detach
fan unit before removing the burn-
er.
Reset device.