Commissioning/service reports
Commissioning/service reports
Settings and test values
Static pressure
Supply pressure (flow pressure)
For natural gas E
For natural gas LL
Tick gas type.
Carbon dioxide content CO
At lower heating output
■
At upper heating output
■
Oxygen content O
*3
2
At lower heating output
■
At upper heating output
■
Carbon monoxide content CO
At lower heating output
■
At upper heating output
■
Fuel cell module
Electrical output
■
Power generated
■
Amount of gas consumed
■
Hours run
■
Distilled water cartridge replaced
■
Air filter A replaced
■
Air filter B replaced
■
CO sensor replaced
■
If the fuel cell module is in operation when the measurement is taken, the result may be below the set value.
*2
If the fuel cell module is in operation when the measurement is taken, the result may be above the set value.
*3
162
Set val-
ue
Date
Signa-
ture
mbar
30
≤
kPa
3.0
≤
mbar
17.4-25
kPa
1.74-2.5
*2
2
% by
7.4-9.5
vol.
% by
7.4-9.5
vol.
% by
4.0-7.6
vol.
% by
4.0-7.6
vol.
ppm
< 1000
ppm
< 1000
W
750
kWh
3
m
h
Commis-
Mainte-
sioning
nance/
service
Mainte-
Mainte-
nance/
nance/serv-
service
ice