Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors page 97

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

Heating circuit 1, Heating circuit 2, Heating...
428.4 "Duration for set flow temperature increase, heating circuit 3"
Setting
60 min
430.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 4"
Setting
0 K
430.4 "Duration for set flow temperature increase, heating circuit 4"
Setting
60 min
933.3 "Priority, DHW heating, heating circuit 1"
Setting
OFF
DHW
933.7 "Room influence factor, heating circuit 1"
Setting
(cont.)
Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60
Delivered condition 60 min
0 to 120
Temperature rise adjustable from 0 to 120 min
Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0
Delivered condition increase 0 K
0 to 20
Temperature rise adjustable from 0 to 20 K
Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60
Delivered condition 60 min
0 to 120
Temperature rise adjustable from 0 to 120 min
Explanations
Priority of DHW heating over the heating circuit
Note
If several heating circuits are connected, only adjusta-
ble in conjunction with low loss header.
0
Without DHW heating priority
1
With DHW heating priority
Explanations
The higher the value, the greater the influence of the
room temperature on the set flow temperature of the
heating circuit (heating curve). Operation with room
temperature hook-up must be set for the heating cir-
cuit (parameter 933.6). Only change the value for sys-
tems with one heating circuit.
For a sample calculation, see chapter "Heating curve"
in the "Function description"
8
Room influence factor
0 to 64
Room influence adjustable from 0 to 64
System configuration (parameters)
97