Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors page 126

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

Troubleshooting
Fault messages on the gas condensing...
Control unit
System characteristics
message
F.377
Burner in a fault state
F.378
Burner in a fault state
126
(cont.)
Cause
Post-processing of ionisa-
tion adjustment: Stabilisa-
tion conditions for post-
calibration not met
Flame loss in the stabilisa-
tion or operating phase
Measures
Check ionisation electrode and
connecting cable. Check plug-in
connection for loose connections.
Check flue system or flue gas re-
circulation.
Check if condensate banked.
Visually inspect gas train inlet and
strainer on the inlet side for con-
tamination.
Note
To prevent water damage, detach
fan unit before removing the burn-
er.
Note
Deposits on the electrodes indicate
foreign bodies in the combustion
air. Check the installation room and
flue system for causes of the de-
posits. For example: Laundry de-
tergents, cleaning agents, toilet-
ries, deposits in the ventilation air
supply (chimney).
If burner gauze assembly and ioni-
sation electrode have been re-
placed, also clean fan unit, gas/air
channel and Venturi extension.
Reset device.
Check gas supply (gas pressure
and gas flow switch).
Check gas train.
Check if condensate banked.
Note
To prevent water damage, de-
tach fan unit before removing the
burner.
Check ionisation electrode and
connecting cable.
Check ignition:
Connecting cables to ignition
module and ignition electrode
Ignition electrode clearance and
contamination: See page 79.
Check ignition electrode for bro-
ken ceramic.
Reset device.