Pressure Sensor Check - Daikin SkyAir RZR-TA Series Service Manual

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

Check

5.11 Pressure Sensor Check

CHECK 12
Detected Pressure
P
, P
H
2
(psi)
(kg/cm
)
(MPa)
725
51.0
653
45.9
580
40.8
508
35.7
435
30.6
363
25.5
290
20.4
218
15.3
145
10.2
72.5
5.1
0
0
–72.5
–5.1
Voltage Measurement Point of the High Pressure Sensor
Voltage Measurement Point of the Low Pressure Sensor
304
L
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0
–0.5
–0.5 0
0.5
1
1.5
Output Voltage V
Main PCB (A1P)
Microcomputer
A/D input
Measure DC voltage between these wires.
Main PCB (A1P)
Microcomputer
A/D input
Measure DC voltage between these wires.
P
(MPa) =
H
P
(MPa) =
L
1 MPa = 145 psi
P
: High pressure (MPa)
H
P
: Low pressure (MPa)
L
High Pressure (P
)
H
V
: Output Voltage (High Side) (VDC)
H
V
: Output Voltage (Low Side) (VDC)
L
Low Pressure (P
)
L
2
2.5
3
3.5
4
(VDC)
, V
H
L
+5 V
X17A
(red)
+5 V
X18A
(blue)
(4)
(3)
(2)
(1)
4.15
4.15
× V
× 0.5
H
3.0
3.0
1.7
1.7
× V
× 0.5
L
3.0
3.0
(4)
Red
High
(3)
Black
pressure
sensor
(2)
White
(1)
Red
Black
Low
pressure
White
sensor
Part 6 Service Diagnosis
SiUS281811EA