Daikin SkyAir RZR-TA Series Service Manual page 308

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

Check
Thermistor temperature
(°C)
(°F)
–30
–22
–25
–13
–20
–4
–15
5
–10
14
–5
23
0
32
5
41
10
50
15
59
20
68
25
77
30
86
35
95
40
104
45
113
50
122
55
131
60
140
65
149
70
158
75
167
80
176
85
185
90
194
95
203
100
212
105
221
Drawing No.
∗The data is for reference purpose only.
302
Type A
Type B
363.8
361.7719
266.8
265.4704
197.8
196.9198
148.2
147.5687
112.0
111.6578
85.52
85.2610
65.84
65.6705
51.05
50.9947
39.91
39.9149
31.44
31.4796
24.95
25.0060
19.94
20.0000
16.04
16.1008
12.99
13.0426
10.58
10.6281
8.669
8.7097
7.143
7.1764
5.918
5.9407
4.928
4.9439
4.123
4.1352
3.467
3.4757
2.9349
2.4894
2.1205
1.8138
1.5575
1.339
1.3425
1.1614
3SA48002
3SA48004
3SA48001
3SA48018
(AD87A001)
3SA48019
(AD94A045)
Resistance (kΩ)
Type C
111.8
85.42
65.80
51.07
39.97
31.51
25.02
20.00
16.10
13.04
10.63
8.711
7.179
3SA48016
(AD100008)
SiUS281811EA
Type E
362.4862
265.9943
197.3083
147.8597
111.8780
85.4291
65.8000
51.0954
39.9938
31.5417
25.0554
20.0395
16.1326
13.0683
10.6490
8.7269
7.1905
5.9524
4.9536
4.1434
3.4825
2.9407
2.4943
2.1247
1.8173
1.5605
1.3451
1.1636
3PA50504
(AD87A001)
Part 6 Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents