SiUS281811EA
4.23 Blower Motor HP Mismatch
C6-01
Error Code
Applicable
FTQ-TA
Models
Outline
Error is issued if the manufacturer ID and output of the connected fan motor do not match those
recognized by the indoor unit.
Error Decision
Gathers information on the manufacturer ID and output of the fan motor when initializing the fan
Conditions
motor.
If those figures are not the values recognized by the indoor unit, it will be deemed abnormal
operation.
If deemed abnormal operation, it will keep retrying until the figures match.
Error Reset
If the manufacturer ID and output match, the error will be cleared.
Conditions
Supposed
Incorrect size motor
Indoor unit capacity setting error
Causes
Corrective
Correct motor installation.
Actions
Correct the indoor unit capacity setting.
Part 6 Service Diagnosis
Troubleshooting by Error Codes
243