Freeze-Up Prevention - Daikin SkyAir RZR-TA Series Service Manual

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

Outline of Control (Indoor Unit)
6.8

Freeze-Up Prevention

Freeze-Up Prevention by Off Cycle (Indoor Unit Individual Control)
When the temperature detected by the liquid pipe temperature thermistor of the indoor heat
exchanger drops too low, the unit enters freeze-up prevention control in accordance with the
following conditions, and is also set in accordance with the conditions given below. (Thermostat
OFF)
When freeze-up prevention is activated, the electronic expansion valve is closed, the drain pump
turns on and the airflow rate is fixed to L tap. When the following conditions for cancelling are
satisfied, it will reset.
Conditions for starting:
Liquid pipe temperature ≤ – 1°C (30.2°F) (for total of 40 minutes)
or
Liquid pipe temperature ≤ – 5°C (23°F) (for total of 10 minutes)
Condition for cancelling:
Liquid pipe temperature ≥ +7°C (44.6°F) (for 10 minutes continuously)
Liquid pipe
temperature
+7ºC
(44.6°F)
0ºC
(32°F)
–5ºC
(23°F)
OR
+7ºC
(44.6°F)
0ºC
(32°F)
–1ºC
(30.2°F)
Concept of freeze-up prevention control
System avoids freeze-up
When freeze-up prevention control starts, system makes sure the frost is completely removed.
134
10 min.
Start
t1
t2
t3
 For comfort, system avoids unnecessary thermostat ON/OFF
 For ensuring compressor reliability, system avoids unnecessary compressor ON/OFF
 System avoids water leakage.
10 min.
Freeze-up prevention control
Forced OFF by thermostat
10 min.
Freeze-up prevention control
Forced OFF by thermostat
t4
t > 40 minutes
Start
SiUS281811EA
Normal operation
Cancel
Normal operation
Cancel
Part 4 Functions and Control