Field Setting from Remote Controller
1.6

Operation Control Mode

The operation control mode is compatible with a variety of controls and operations by limiting the
functions of the operation remote controller. Furthermore, operations such as remote controller
ON/OFF can be limited in accordance with the combination conditions. (Refer to information in the
next page.)
Centralized controller is normally available for operations. (Except when centralized monitor is
connected)
Contents of Control Modes
20 modes consisting of combinations of the following 5 operation modes with temperature and
operation mode setting by remote controller can be set and displayed by operation modes 0
through 19.
 ON/OFF control impossible by remote controller
 OFF control only possible by remote controller
 Centralized
 Individual
 Timer operation possible by remote controller
168
Used when you want to turn ON/OFF by centralized remote controller only.
(Cannot be turned ON/OFF by remote controller.)
Used when you want to turn ON by centralized remote controller only, and OFF by remote
controller only.
Used when you want to turn ON by centralized remote controller only, and turn ON/OFF
freely by remote controller during set time.
Used when you want to turn ON/OFF by both centralized remote controller and remote
controller.
Used when you want to turn ON/OFF by remote controller during set time and you do not want
to start operation by centralized remote controller when time of system start is programmed.
SiUS281811EA
Part 5 Field Settings and Test Operation