Daikin SkyAir RZR-TA Series Service Manual page 169

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811EA
1.5.22 Swing Pattern Settings
(For units with an infrared floor sensor)
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed side
by side are set to swing in an opposite direction to agitate airflow to reduce temperature irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
Mode
13 (23)
1.5.23 Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
 FCQ-TA, FAQ-TA
Mode
13 (23)
Note(s)
When the model FCQ-TA is attached with a closing member kit, set the Second Code No. to 02 or
03.
1.5.24 External Static Pressure Settings
Make external static pressure setting automatically using automatic airflow adjustment, or manually
using external static pressure settings.
 FBQ-P
Make sure that 11 (21)-7 (Airflow adjustment) is set to 01 (OFF).
Part 5 Field Settings and Test Operation
First Code
Second Code
No.
No.
No.
01
2
02
03
First Code
Second Code
No.
No.
No.
01
4
02
03
Mode No.
First Code No.
13 (23)
6
Field Setting from Remote Controller
Contents
All direction synchronized swing
Facing swing
Contents
Draft prevention (Upward)
Standard
Ceiling soiling prevention (Downward)
Second Code No.
02
03
04
05
06
07
08
09
10
11
12
13
14
15
: Factory setting
: Factory setting
: Factory setting
Contents
50 Pa (0.20 inWG)
60 Pa (0.24 inWG)
70 Pa (0.28 inWG)
80 Pa (0.32 inWG)
90 Pa (0.36 inWG)
100 Pa (0.40 inWG)
110 Pa (0.44 inWG)
120 Pa (0.48 inWG)
130 Pa (0.52 inWG)
140 Pa (0.56 inWG)
150 Pa (0.60 inWG)
160 Pa (0.64 inWG)
180 Pa (0.72 inWG)
200 Pa (0.80 inWG)
163