Details Of Field Settings For Indoor Unit - Daikin SkyAir RZR-TA Series Service Manual

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811EA
1.5

Details of Field Settings for Indoor Unit

1.5.1 Filter Cleaning Sign Interval, Filter Type
When the setting 10 (20)-3 is set to 01 (Displayed), filter cleaning sign is displayed on the remote
controller after a certain period of operation time. This setting is used to change the display interval
of filter cleaning sign when the filter contamination is heavy.
The filter cleaning sign interval is determined as follows depending on the combination of Mode No.
10 (20)-0 and 10 (20)-1.
Setting
Model
Setting
Model
1.5.2 Thermistor Selection
Select a thermistor to control the room temperature.
When the unit is not equipped with an infrared floor sensor:
Mode
10 (20)
The factory setting for the Second code No. is 01 and room temperature is controlled by the suction
air thermistor for indoor unit and remote controller thermistor. When the Second code No. is set to
02, room temperature is controlled by the suction air thermistor. When the Second code No. is set
to 03, room temperature is controlled by the remote controller thermistor.
 FTQ-TA
When the Second Code No. is set to 02, room temperature is controlled by the remote sensor
thermistor. When the Second Code No. is set to 03, room temperature is controlled by the remote
controller thermistor.
Part 5 Field Settings and Test Operation
10 (20)-1
Filter contamination
heavy/light 10 (20)-0
FCQ-TA
FHQ-P
FHQ-M
FBQ-P
FAQ-TA
10 (20)-1
Filter contamination
heavy/light 10 (20)-0
FTQ-TA
First Code
Second
No.
No.
Code No.
01
2
02
03
Mode No.
First Code No.
10 (20)
2
Field Setting from Remote Controller
01: Long life filter
Light
Heavy
01
02
2,500 hrs.
1,250 hrs.
200 hrs.
100 hrs.
01: Short interval
Light
Heavy
01
02
2,500 hrs.
1,250 hrs.
Contents
Remote controller thermistor and suction air thermistor for
indoor unit
Suction air thermistor for indoor unit
Remote controller thermistor
Second Code No.
01
02
03
Remote controller thermistor
: Factory setting
02: Ultra long life filter
Light
Heavy
01
02
10,000 hrs.
5,000 hrs.
200 hrs.
100 hrs.
: Factory setting
02: Long interval
Light
Heavy
01
02
10,000 hrs.
5,000 hrs.
: Factory setting
: Factory setting
Contents
Remote sensor thermistor
153

Hide quick links:

Advertisement

Table of Contents