SiUS281811EA
4.29 Activation of High Pressure Switch
E3
Error Code
Applicable
All outdoor units
Models
Method of Error
Abnormality is detected when the contact of the high pressure switch opens.
Detection
Use the protection device circuit to test high pressure switch conduction.
Error Decision
Part of the protection device has an open circuit.
Conditions
Error is generated when the high pressure switch activation count reaches the number specific to
the operation mode.
Reference
Operating pressure: 4.0 MPa (580 psi)
Reset pressure: 3.0 MPa (435 psi)
Supposed
Activation of outdoor unit high pressure switch
Causes
Defective high pressure switch
Defective outdoor main PCB
Instantaneous power failure
Defective high pressure sensor
Part 6 Service Diagnosis
Troubleshooting by Error Codes
253