When Turning On Power First Time; When Turning On Power The Second Time And Subsequent; When An Indoor Unit Or Outdoor Unit Has Been Added, Or Indoor Or Outdoor Unit Pcb Has Been Changed - Daikin SkyAir RZR-TA Series Service Manual

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811EA
3.5

When Turning ON Power First Time

The unit cannot be run for up to 12 minutes to automatically set the master power and address
(indoor-outdoor address, etc.).
Status
Outdoor unit
Indoor unit
3.6
When Turning ON Power the Second Time and
Subsequent
Tap the RESET (BS5) button on the outdoor unit PCB. Operation becomes possible for about 2
minutes. If you do not push the RESET (BS5) button, the unit cannot be run for up to 10 minutes to
automatically set master power.
Status
Outdoor unit
Indoor unit
3.7
When an Indoor Unit or Outdoor Unit has been Added, or
Indoor or Outdoor Unit PCB has been Changed
Be sure to push and hold the RESET (BS5) button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outdoor address, etc.)
Status
Outdoor unit
Indoor unit
Part 5 Field Settings and Test Operation
Test lamp H2P .... Blinks
Can also be set during operation described above.
If ON button is pushed during operation described above, the UH error indicator
blinks. (Returns to normal when automatic setting is complete.)
Test lamp H2P .... Blinks
Can also be set during operation described above.
If ON button is pushed during operation described above, the operation lamp
lights but the compressor does not operate. (Returns to normal when automatic
setting is complete.)
Test lamp H2P .... ON
Can also be set during operation described above.
If ON button is pushed during operation described above, the UH or U4 error
indicator blinks. (Returns to normal when automatic setting is complete.)
Test Operation