Blower Motor Not Running - Daikin SkyAir RZR-TA Series Service Manual

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811EA

4.10 Blower Motor Not Running

A6
Error Code
Applicable
FTQ-TA
Models
Outline
Error is issued if the indoor unit determines that the indoor fan motor cannot rotate.
Error Decision
 Determining successive abnormalities
Conditions
 Determining long-term abnormalities
Error Reset
Reset by remote controller
Conditions
Supposed
 Fan or motor obstruction
Causes
 Power interruption (low voltage)
 Incorrect or loose wiring
Corrective
 Check for obstruction on the fan or motor.
Actions
 Verify the input voltage at the motor.
 Check wiring or tighten wiring connections if needed.
 Replace the indoor unit PCB or motor.
Reference
CHECK 19 Refer to page 311.
Part 6 Service Diagnosis
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
If that figure falls below 50 rpm 5 times successively, it is deemed abnormal operation.
If, during operation, the rotation command is stopped, the 5-second interval check is halted and
the counted number will be cleared.
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
Performs rotation sampling 720 times (takes approx. one hour), and if the rotation speed falls
below 50 rpm over 100 times, it is deemed abnormal operation.
When the sampling reaches 720 times, the counted number will be cleared and the 720 times
sampling restarts.
If, during this, the rotation command is stopped, the 5-second interval check is halted, but the
counted number will be kept.
When the rotation command is restarted, the checks will resume.
Troubleshooting by Error Codes